Over-temperature protection¶
Verifies the battery system's overheat protection terminates or limits operation before thermal damage occurs — exercises the BMS thermal-cutoff logic under combined ambient and charge/discharge thermal load.
| Clause (method) | 8.2.11 |
| Clause (pass criteria) | 5.2.11 |
| Object | system |
| Status vs. 2020 | revised |
| Observation period | 1 h at test environment temperature |
Pass criteria¶
After the over-temperature protection test, the battery system shall show no leakage, no housing crack, no fire, and no explosion. The insulation resistance after testing shall not be less than 100 Ω/V (DC), or 500 Ω/V if an AC circuit is present.
Source: GB 38031-2025, clause 5.2.11 (PDF p. 12).
Pre-conditions¶
- Object: The test object is a battery system (not a bare pack). (8.2.11.1)
- Pre-treatment: Standard, per clause 7.2.
- SOC: Highest working SOC per clause 6.1.10.
- Protection devices: All protection devices that affect the function of the test object and are related to the test results, except for the cooling system, shall be in normal operating condition. (8.2.11.2)
- Insulation baseline: Measure before the test per Appendix B (clause 6.1.5).
Test parameters¶
| Parameter | Value | Source |
|---|---|---|
| Initial chamber temperature | 20 °C ± 10 °C (or higher per manufacturer) | 8.2.11.4 |
| Chamber target (with overheat protection) | Manufacturer's overheat-protection operating-temperature threshold | 8.2.11.4 a) |
| Chamber target (without overheat protection) | Manufacturer's maximum operating temperature | 8.2.11.4 b) |
| Forcing current | Continuous charge/discharge to drive cell T up as fast as possible within mfr normal operating range | 8.2.11.3 |
| Cooling system | Disabled (other protections active) | 8.2.11.2 |
| Termination conditions | Auto cutoff / manufacturer signal / T stable (ΔT < 4 °C over 2 h) | 8.2.11.5 |
| Post-test observation | 1 h at test environment temperature | 8.2.11.6 |
Procedure¶
- Confirm pre-treatment per 7.2 and measure baseline insulation per Appendix B. (6.1.5)
- Adjust SOC to highest working value. (6.1.10)
- Confirm all protection devices except the cooling system are in normal operating condition. (8.2.11.2)
- Place the test object in a temperature chamber and connect external charging/discharging equipment.
- Begin continuous charge and discharge with current sized to drive cell temperature up as quickly as possible within the manufacturer's normal operating range. (8.2.11.3)
- Gradually ramp the chamber temperature from 20 °C ± 10 °C (or higher per manufacturer) to:
- the manufacturer's overheat-protection operating-temperature threshold (if equipped), or
- the manufacturer's maximum operating temperature (if no overheat protection). (8.2.11.4)
- Maintain that temperature (or higher) until any termination condition is met. (8.2.11.4, 8.2.11.5)
- Terminate when any of the following occurs: a. The test object automatically terminates or limits charging/discharging. b. The test object sends a signal to terminate or limit charging/discharging. c. The test object's temperature stabilizes (ΔT < 4 °C over 2 h). (8.2.11.5)
- Observe the test object at the test environment temperature for 1 hour. (8.2.11.6)
- Re-measure insulation per Appendix B; inspect for leakage, housing cracks; confirm no fire/explosion.
After-test observation¶
Observe the test object for 1 hour at the test environment temperature (22 °C ± 5 °C) after the termination condition is met. (8.2.11.6)
What changed from GB 38031-2020¶
- Listed in the preface change list as both requirements (5.2.11) and method (8.2.11) revised.
Migration impact: Already-type-approved vehicle models must comply from 2027-08-01. New type approvals from 2026-07-01. See Re-certification timeline.
Engineering notes (non-normative)¶
The notes below are practical interpretation, not part of the standard.
Engineering note (non-normative): The test exercises the BMS thermal-protection path, not cell thermal stability. With the cooling system disabled and current driving heat in, the question is whether the BMS de-rates or cuts off before damage. A pack that finishes the test on the temperature-stable termination (option c) — rather than on auto-cutoff — has demonstrated that its thermal management absorbs the worst case without needing protection to fire, which is a stronger result.
Engineering note (non-normative): "Continuous charging and discharging" is intentionally vague — the manufacturer chooses the rate to maximize heating within the normal operating envelope. Document the chosen current profile; type-approval reviewers will scrutinize whether the rate is genuinely aggressive or a soft case that lets the BMS off easy.
Related¶
- Pass/fail criteria: What "no fire, no explosion" means, Insulation resistance thresholds
- Glossary: Housing crack, Leakage, BMS
- Referenced standards: (none specifically cited in 8.2.11)
- Related tests: Over-current protection (8.2.12), External short-circuit protection (8.2.13), Overcharge protection (8.2.14), Over-discharge protection (8.2.15)
- Source: GB 38031-2025, clause 8.2.11 (PDF p. 25–26); pass criteria in clause 5.2.11 (PDF p. 12).