Over-current protection¶
Verifies the battery system's over-current protection cuts off or limits charging when an external DC supply faults to a higher current than the system is rated for.
| Clause (method) | 8.2.12 |
| Clause (pass criteria) | 5.2.12 |
| Object | system |
| Status vs. 2020 | revised |
| Observation period | 1 h at test environment temperature |
Pass criteria¶
After the over-current protection test, the battery system shall show no leakage, no housing crack, no fire, and no explosion. The insulation resistance after testing shall not be less than 100 Ω/V (DC), or 500 Ω/V if an AC circuit is present.
Source: GB 38031-2025, clause 5.2.12 (PDF p. 12).
Pre-conditions¶
- Object: The test object is a battery system powered by an external DC power supply. (8.2.12.1)
- Ambient temperature: 20 °C ± 10 °C. (8.2.12.2 a)
- SOC: Adjust to the middle of the manufacturer-recommended normal operating range (precise adjustment not required as long as the system can operate normally). (8.2.12.2 b)
- Over-current and maximum voltage: Determined in consultation with the battery system manufacturer, assuming failure of the external DC power supply. (8.2.12.2 c)
- Insulation baseline: Measure before the test per Appendix B (clause 6.1.5).
Test parameters¶
| Parameter | Value | Source |
|---|---|---|
| Ambient temperature | 20 °C ± 10 °C | 8.2.12.2 a) |
| SOC | Mid-SOC (middle of normal operating range) | 8.2.12.2 b) |
| Power source | External DC power supply | 8.2.12.1 |
| Initial charging current | Manufacturer's maximum normal charging current | 8.2.12.3 b) |
| Over-current level | Per manufacturer (assuming external DC supply failure) | 8.2.12.2 c) |
| Ramp time (normal → over-current) | ≤ 5 s | 8.2.12.3 b) |
| Charging-control communication | Changed or disabled to allow over-current | 8.2.12.3 a) |
| Termination conditions | Auto cutoff / manufacturer signal / T stable (ΔT < 4 °C over 2 h) | 8.2.12.4 |
| Post-test observation | 1 h at test environment temperature | 8.2.12.5 |
Procedure¶
- Confirm pre-treatment per 7.2 and measure baseline insulation per Appendix B. (6.1.5)
- Adjust SOC to the middle of the normal operating range. (8.2.12.2 b)
- Bring ambient to 20 °C ± 10 °C. (8.2.12.2 a)
- Connect the external DC power supply equipment.
- Change or disable the charging-control communication so the system will accept the over-current level agreed with the manufacturer. (8.2.12.3 a)
- Start the external DC supply and charge the battery system at the manufacturer's maximum normal charging current. (8.2.12.3 b)
- Within 5 seconds, increase the current from the maximum normal charging current to the agreed over-current level, and continue charging. (8.2.12.3 b)
- Continue until any termination condition is met: a. The test object automatically terminates the charging current. b. The test object sends a signal to terminate the charging current. c. The test object's temperature stabilizes (ΔT < 4 °C over 2 h). (8.2.12.4)
- Observe at the test environment temperature for 1 hour. (8.2.12.5)
- Re-measure insulation per Appendix B; inspect for leakage, housing cracks; confirm no fire/explosion.
After-test observation¶
Observe the test object for 1 hour at the test environment temperature (22 °C ± 5 °C) after the termination condition is met. (8.2.12.5)
What changed from GB 38031-2020¶
- Listed in the preface change list as both requirements (5.2.12) and method (8.2.12) revised.
Migration impact: Already-type-approved vehicle models must comply from 2027-08-01. New type approvals from 2026-07-01. See Re-certification timeline.
Engineering notes (non-normative)¶
The notes below are practical interpretation, not part of the standard.
Engineering note (non-normative): The 5-second ramp from max-normal to over-current is fast enough that BMS protection has to react during the ramp or shortly after. Slow-rolling the ramp would let the system de-rate gracefully — the standard explicitly prevents that. Protection logic with a sliding-window current filter slower than 5 s will likely fail this test even if the steady-state over-current eventually trips.
Engineering note (non-normative): The over-current and maximum voltage are negotiated with the manufacturer "assuming failure of the external DC supply" — i.e., the realistic worst case from a faulted DC charger. This is a written agreement that becomes part of the test record. Pick numbers that represent a credible charger-side fault, not the easiest case to pass.
Related¶
- Pass/fail criteria: What "no fire, no explosion" means, Insulation resistance thresholds
- Glossary: Housing crack, Leakage, BMS
- Referenced standards: (none specifically cited in 8.2.12)
- Related tests: Over-temperature protection (8.2.11), External short-circuit protection (8.2.13), Overcharge protection (8.2.14), Over-discharge protection (8.2.15)
- Source: GB 38031-2025, clause 8.2.12 (PDF p. 26); pass criteria in clause 5.2.12 (PDF p. 12).