External short-circuit protection¶
Verifies the battery system's protection devices interrupt or sustain a low-resistance external short across the high-voltage terminals without losing electrical safety.
| Clause (method) | 8.2.13 |
| Clause (pass criteria) | 5.2.13 |
| Object | system |
| Status vs. 2020 | revised (requirements) |
| Observation period | 1 h at test environment temperature |
Pass criteria¶
After the external short-circuit protection test, the battery system shall show no leakage, no housing crack, no fire, and no explosion. The insulation resistance after testing shall not be less than 100 Ω/V (DC), or 500 Ω/V if an AC circuit is present.
Source: GB 38031-2025, clause 5.2.13 (PDF p. 12).
Pre-conditions¶
- Object: The test object is a battery system. (8.2.13.1)
- Ambient temperature: 20 °C ± 10 °C (or higher if specified by manufacturer). (8.2.13.2 a)
- Protection devices: All protection devices that affect the functionality of the test object and are related to the test results shall be in normal operation at the start. (8.2.13.2 b)
- Contactors: Main contactors used for charging and discharging shall be closed at start (representing operable / external-charging-allowed mode). (8.2.13.3 a)
- Pre-treatment: Standard, per clause 7.2.
- SOC: Highest working SOC per clause 6.1.10.
- Insulation baseline: Measure before the test per Appendix B (clause 6.1.5).
Test parameters¶
| Parameter | Value | Source |
|---|---|---|
| Ambient temperature | 20 °C ± 10 °C (or higher per manufacturer) | 8.2.13.2 a) |
| External short-circuit resistance | ≤ 5 mΩ | 8.2.13.3 b) |
| Connection | Positive ↔ negative terminals shorted together | 8.2.13.3 b) |
| Maintain short until | (a) Protection trips, or (b) Housing T stable (ΔT < 4 °C over 2 h) then continue short for ≥ 1 h more | 8.2.13.4 |
| Multiple trials allowed | Yes — if test cannot complete in a single trial | 8.2.13.3 a) |
| Post-test observation | 1 h at test environment temperature | 8.2.13.5 |
Procedure¶
- Confirm pre-treatment per 7.2 and measure baseline insulation per Appendix B. (6.1.5)
- Adjust SOC to highest working value. (6.1.10)
- Bring ambient to 20 °C ± 10 °C (or higher per manufacturer). (8.2.13.2 a)
- Confirm all relevant protection devices are in normal operation. (8.2.13.2 b)
- Close the main contactors used for charging and discharging. (8.2.13.3 a)
- Connect the positive and negative terminals together with a short-circuit path of resistance ≤ 5 mΩ. (8.2.13.3 b)
- Maintain the short until either: a. The protection function activates and terminates the short-circuit current, or b. The housing temperature stabilizes (ΔT < 4 °C over 2 h), then continue the short for at least 1 hour more. (8.2.13.4)
- If the test cannot be completed in one trial, conduct two or more trials. (8.2.13.3 a)
- Open the short and observe the test object at the test environment temperature for 1 hour. (8.2.13.5)
- Re-measure insulation per Appendix B; inspect for leakage, housing cracks; confirm no fire/explosion.
After-test observation¶
Observe the test object for 1 hour at the test environment temperature (22 °C ± 5 °C) after the short is opened. (8.2.13.5)
What changed from GB 38031-2020¶
- Listed in the preface change list as requirements revised (5.2.13). The test method (8.2.13) is not flagged in the preface as revised.
Migration impact: Already-type-approved vehicle models must comply from 2027-08-01. New type approvals from 2026-07-01. See Re-certification timeline.
Engineering notes (non-normative)¶
The notes below are practical interpretation, not part of the standard.
Engineering note (non-normative): The "tripped or temperature-stable + 1 h more" termination is the headline mechanic. A pyrofuse that opens immediately gives the easiest pass; a system that relies on relay opening also passes if the contactor logic responds. A pack with no protection must instead survive the steady-state short until housing temperature stabilizes plus a one-hour soak — that is a much higher bar and effectively requires the cell-level chemistry plus interconnect impedance to limit current to a sustainable level.
Engineering note (non-normative): The 5 mΩ external-short value is the same value used in the cell-level external-short test (8.1.4). At system-level voltages the corresponding short-circuit currents are very large; specify the bus-bar and load contactor on the test rig accordingly. Multi-trial provision exists because a single trial may consume a fuse or contactor before the test articles are exercised — plan for two trials by default.
Related¶
- Pass/fail criteria: What "no fire, no explosion" means, Insulation resistance thresholds
- Glossary: Housing crack, Leakage, Pyrofuse
- Referenced standards: (none specifically cited in 8.2.13)
- Related tests: Over-temperature protection (8.2.11), Over-current protection (8.2.12), Overcharge protection (8.2.14), Over-discharge protection (8.2.15), Cell-level external short (8.1.4)
- Source: GB 38031-2025, clause 8.2.13 (PDF p. 26); pass criteria in clause 5.2.13 (PDF p. 12).